Tool

Motor & VFD Calculator

Synchronous and full-load RPM from supply frequency and pole count, VFD speed/torque scaling for constant- vs variable-torque loads, belt/gear reduction, and full-load current estimation.

Motor nameplate

Supply frequency

Speed at nameplate

Synchronous RPM180060 Hz, 4 pole
Full-load RPM1750
Slip2.78 %

Power & torque

Rated power5.00 HP3.73 kW
Rated torque15.01 lbf·ft20.34 N·m

Estimated FLA (3-phase)

Full-load amps5.99 A

I = (HP × 746) / (√3 × V × η × PF). Always confirm against the motor nameplate and NEC Table 430.250 for OCPD sizing.

Synchronous RPM reference

Poles60 Hz50 HzFL (typ. 3% slip)
2360030003492 / 2910
4180015001746 / 1455
6120010001164 / 970
8900750873 / 728
10720600698 / 582
12600500582 / 485
14514429499 / 416
16450375437 / 364

VFD operation

Load type
Frequency vs base100.0 %
Sync RPM at drive1800
Shaft RPM at drive1750
Torque at drive20.34 N·m15.01 lbf·ft
Power at drive3.73 kW5.00 HP

Above base frequency (typically 60 Hz here), constant-torque loads enter constant-power region — torque falls inversely with speed. For variable-torque (centrifugal pumps / fans), torque varies with speed squared and power with speed cubed (the affinity laws).

Belt / gear reduction (driven side)

Ratio = driver / driven. Speed scales with the ratio; torque scales inversely. Apply efficiency separately for true output torque (not modeled here).

Ratio0.500 : 1
Driven RPM875.0
Driven torque40.69 N·m30.01 lbf·ft
tool