Tool

Wire Gauge & Ampacity

AWG ↔ mm², NEC ampacity (60/75/90 °C, copper or aluminum), and voltage-drop calculation for single-phase, three-phase, and DC circuits.

Ampacity

25 A

NEC 310.16, 75 °C

Load uses 80% of capacity.

Voltage drop

3.18 V

1.32% of 240 V

Target: ≤3% branch / ≤5% feeder + branch (NEC informational FPN 210.19).

Recommended minimum size

14

2.08 mm² · 20 A ampacity

Voltage drop at this size: 2.10%

Selected conductor details

Size
12
Cross-section
3.31 mm² (7 kcmil)
Diameter
0.0808 in (2.05 mm)
Resistance / kft
1.588 Ω/kft
Resistance at length
79.40 mΩ (one-way)

Ampacity for this size (copper)

60 °C (TW)
20 A
75 °C (THW)
25 A
90 °C (THHN)
30 A
75 °C aluminum
20 A

Base values from NEC Table 310.16, ≤3 current-carrying conductors in a raceway. Apply derating for ambient temperature and conduit fill per NEC 310.15.

Quick AWG reference table

AWGmm²Ø inΩ/kft (Cu)60 °C75 °C90 °C
180.820.04036.385071014
161.310.05084.0160101318
142.080.06412.5250152025
123.310.08081.5880202530
105.260.10190.9990303540
88.370.12850.6280405055
613.300.16200.3950556575
421.150.20430.2490708595
326.670.22940.197085100115
233.620.25760.156095115130
142.410.28930.1240110130145
1/053.490.32490.0983125150170
2/067.430.36480.0779145175195
3/085.010.40960.0618165200225
4/0107.200.46000.0490195230260
250 kcmil127.000.50000.0415215255290
300 kcmil152.000.54770.0346240285320
350 kcmil177.000.59160.0297260310350
400 kcmil203.000.63250.0260280335380
500 kcmil253.000.70710.0208320380430
600 kcmil304.000.77460.0173350420475
750 kcmil380.000.86600.0139400475535
1000 kcmil507.001.00000.0104455545615

Values are simplified from NEC Table 310.16 (US) for general-purpose sizing. Always verify against the current code edition, the controlling jurisdiction’s amendments, and the actual cable manufacturer’s datasheet for the installation conditions (ambient temperature, conduit fill, termination ratings).